| ACKL |
MEDIA FOR WHICH DESIGNED |
REFRIGERANT VAPOR |
| AWWH |
WATER SIDE TEST MINIMUM PRESSURE |
270.0 POUNDS PER SQUARE INCH |
| ARGE |
HEAD MATERIAL |
STEEL |
| AGAV |
END ITEM IDENTIFICATION |
CVN72-75 SHIPS WITH CENTRIFUGAL COMPRESSOR CHILLED WATER AIR CONDITIONER |
| AEUG |
SHELL MATERIAL |
STEEL |
| AWLA |
REFRIGERANT INLET CONNECTION SIZE |
10 INCH |
| AWGJ |
TUBE MATERIAL |
COPPER NICKEL ALLOY |
| AWGK |
TUBE EFFECTIVE LENGTH |
156.250 INCHES |
| AWLB |
REFRIGERANT OUTLET CONNECTION QUANTITY |
2 |
| ABHP |
OVERALL LENGTH |
156.250 INCHES NOMINAL |
| ARNF |
TUBE QUANTITY |
387 |
| AWKX |
REFRIGERANT INLET CONNECTION QUANTITY |
1 |
| AWLD |
REFRIGERANT OUTLET CONNECTION SIZE |
6 INCH |
| AWGE |
PASS QUANTITY |
1 |
| AWWG |
REFRIGERANT SIDE TEST MINIMUM PRESSURE |
30.0 POUNDS PER SQUARE INCH |
| AWCD |
WATER FOR WHICH DESIGNED |
SALT |
| AWKW |
WATER CONNECTION TYPE |
FLANGED, ENDS SEALED |
| ABMK |
OVERALL WIDTH |
26.000 INCHES NOMINAL |
| AAYE |
REFRIGERATION FLOW RATE IN TONS PER HOUR |
387.000 |
| FEAT |
SPECIAL FEATURES |
FOR MIL-R-24085 REFRIGERATION UNITS CONVERTED FROM CFC-114 TO HFC-236A |
| AWKZ |
WATER CONNECTION SIZE |
17.51 INCH |
| AWLC |
REFRIGERANT OUTLET CONNECTION TYPE |
FLANGE |
| AWKY |
REFRIGERANT INLET CONNECTION TYPE |
FLANGE |
| AWKT |
WATER CONNECTION QUANTITY |
2 |
| AWKR |
SHELL LENGTH |
149.500 INCHES |
| CWTS |
WATER FLOW RATE |
1633.5 GALLONS PER MINUTE |
| AWKS |
SHELL OUTSIDE DIAMETER |
24.000 INCHES |
| AYTS |
COOLING TYPE |
WATER |
| AWGL |
TUBE FIN |
PROVIDED |