| CSWP |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS |
125.0 AC AND 50.0 DC |
| AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
3.239 INCHES NOMINAL |
| CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
1.021 INCHES MINIMUM AND 1.041 INCHES MAXIMUM |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
2 TOGGLE |
| CPRZ |
AUXILIARY SWITCH FUNCTION AND QUANTITY |
1 ALARM |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
47.0 AMPERES AC ALL LOCATIONS |
| AKPX |
POLE QUANTITY |
2 |
| ADAQ |
BODY LENGTH |
3.709 INCHES MINIMUM AND 3.729 INCHES MAXIMUM |
| AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
| CSSX |
SWITCH CURRENT RATING AND TYPE IN AMPS |
5.0 AC AND 1.0 DC |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
1500.0 AC ALL LOCATIONS |
| TTQY |
TERMINAL TYPE AND QUANTITY |
4 THREADED STUD |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
| AEGJ |
SWITCH CONTACT ARRANGEMENT |
SINGLE POLE, DOUBLE THROW |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 THREADED HOLE |
| CQSM |
SWITCH LOCATION AND POSITION DESIGNATION |
INTERNAL AT POLE ONE |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
DUSTPROOF AND FUNGUS PROOF |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
1.021 INCHES MINIMUM AND 1.041 INCHES MAXIMUM |
| ADAT |
BODY WIDTH |
2.021 INCHES MINIMUM AND 2.041 INCHES MAXIMUM |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CPRQ |
RESET METHOD |
MANUAL |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
2.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
3.053 INCHES MINIMUM AND 3.073 INCHES MAXIMUM |
| THSD |
THREAD SERIES DESIGNATOR |
UNC |
| CPRJ |
TRIP RELEASE METHOD |
MAGNETIC-HYDRAULIC ALL LOCATIONS |
| CRTK |
SWITCH TERMINAL TYPE |
TAB, SOLDER LUG |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| APNQ |
ARC QUENCHING METHOD |
MAGNETIC BLOWOUT |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
| AJEC |
BOSS HEIGHT |
0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM |
| AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
250.0 AC ALL LOCATIONS |
| CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE AND TWO LINKED |
| CMLP |
THREAD QUANTITY PER INCH |
32 |
| CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |