ABKW |
OVERALL HEIGHT |
3.170 INCHES NOMINAL |
FREQ |
FREQUENCY IN HERTZ |
60.0 SINGLE LOCATION |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT SINGLE LOCATION |
CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS SINGLE LOCATION AND TIME DELAY SINGLE LOCATION |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
125.0 AC SINGLE LOCATION |
TTQY |
TERMINAL TYPE AND QUANTITY |
2 THREADED STUD |
ABHP |
OVERALL LENGTH |
2.500 INCHES NOMINAL |
CQQC |
TRIP RELEASE DUTY CYCLE |
CONTINUOUS SINGLE LOCATION |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRJ |
TRIP RELEASE METHOD |
MAGNETIC SINGLE LOCATION |
ADTV |
CASE MATERIAL |
PLASTIC |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
7.000 MINIMUM AT 150 PCT SINGLE LOCATION AND 1.000 MAXIMUM AT 500 PCT SINGLE LOCATION AND 1.200 MINIMUM AT 300 PCT SINGLE LOCATION AND 9.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 0.300 MINIMUM AT 500 PCT SINGLE LOCATION AND 3.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 0.010 MINIMUM AT 1000 PCT SINGLE LOCATION AND 3.500 MAXIMUM AT 300 PCT SINGLE LOCATION AND 25.000 MAXIMUM AT 150 PCT SINGLE LOCATION AND 0.040 MAXIMUM AT 1000 PCT SINGLE LOCATION |
AKPX |
POLE QUANTITY |
1 |
CPRQ |
RESET METHOD |
MANUAL |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
6.0 AMPERES AC SINGLE LOCATION |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
2 THREADED HOLE |
APNQ |
ARC QUENCHING METHOD |
MAGNETIC BLOWOUT |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
ABMK |
OVERALL WIDTH |
0.750 INCHES NOMINAL |
CMLP |
THREAD QUANTITY PER INCH |
32 |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
DUSTPROOF |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
2000.0 AC SINGLE LOCATION |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 SINGLE LOCATION |
FEAT |
SPECIAL FEATURES |
MTG HOLES ON 2 1/16 IN. CENTERS |
CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |