| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
100.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 800.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE TWO |
| AKPX |
POLE QUANTITY |
3 |
| AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
| ABHP |
OVERALL LENGTH |
9.938 INCHES MINIMUM AND 10.063 INCHES MAXIMUM |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
| ABKW |
OVERALL HEIGHT |
3.688 INCHES MINIMUM AND 3.813 INCHES MAXIMUM |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
240.0 AC ALL LOCATIONS |
| ABMK |
OVERALL WIDTH |
3.968 INCHES MINIMUM AND 4.094 INCHES MAXIMUM |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| AAQL |
BODY STYLE |
RECTANGULAR DIMENSIONAL ENVELOPE |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
CORROSION RESISTANT AND SHOCK RESISTANT |
| CPRQ |
RESET METHOD |
MANUAL |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| TTQY |
TERMINAL TYPE AND QUANTITY |
3 COMPRESSION AND 3 TAB W/SCREW |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
3 TERMINAL |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
225.0 AMPERES AC ALL LOCATIONS |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
25000.0 AC ALL LOCATIONS |