CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
1.500 MINIMUM AT 300 PCT ALL LOCATIONS AND 31.000 MAXIMUM AT 150 PCT ALL LOCATIONS AND 7.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 4.000 MAXIMUM AT 300 PCT ALL LOCATIONS AND 0.600 MINIMUM AT 325 PCT ALL LOCATIONS AND 2.000 MAXIMUM AT 325 PCT ALL LOCATIONS |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
1000.0 AC ALL LOCATIONS |
FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
AKPX |
POLE QUANTITY |
2 |
TTQY |
TERMINAL TYPE AND QUANTITY |
4 THREADED STUD |
ABMK |
OVERALL WIDTH |
2.530 INCHES NOMINAL |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
ABKW |
OVERALL HEIGHT |
1.530 INCHES NOMINAL |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 THREADED HOLE |
ADTV |
CASE MATERIAL |
PLASTIC |
AAQL |
BODY STYLE |
RECTANGULAR DIMENSIONAL ENVELOPE |
CPRQ |
RESET METHOD |
MANUAL |
THSD |
THREAD SERIES DESIGNATOR |
UNC |
CPRJ |
TRIP RELEASE METHOD |
MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
ABHP |
OVERALL LENGTH |
3.330 INCHES NOMINAL |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
250.0 AC ALL LOCATIONS |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
CMLP |
THREAD QUANTITY PER INCH |
32 |
CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
50.0 AMPERES AC ALL LOCATIONS |