BBRJ |
SPECIAL HANDLING FEATURE |
MAGNETIC |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 UNTHREADED HOLE |
FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
ADAT |
BODY WIDTH |
4.500 INCHES NOMINAL |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE TWO |
AKPX |
POLE QUANTITY |
3 |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
100000.0 AC ALL LOCATIONS |
ADAU |
BODY HEIGHT |
4.063 INCHES NOMINAL |
AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
AJEC |
BOSS HEIGHT |
0.187 INCHES NOMINAL |
AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
1.500 INCHES NOMINAL |
AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
10.687 INCHES NOMINAL |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
8.687 INCHES NOMINAL |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT |
ADTV |
CASE MATERIAL |
PLASTIC |
CPRQ |
RESET METHOD |
MANUAL |
AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.250 INCHES NOMINAL |
AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
1.500 INCHES NOMINAL |
TTQY |
TERMINAL TYPE AND QUANTITY |
6 COMPRESSION |
CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
90.0 AMPERES AC ALL LOCATIONS |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ |
BODY LENGTH |
11.937 INCHES NOMINAL |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
600.0 AC ALL LOCATIONS |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
0.400 MINIMUM AT 200 PCT ALL LOCATIONS AND 4.500 MAXIMUM AT 200 PCT ALL LOCATIONS |