| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 UNTHREADED HOLE |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
800.0 AMPERES AC ALL LOCATIONS |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| AKPX |
POLE QUANTITY |
3 |
| ADAQ |
BODY LENGTH |
17.000 INCHES NOMINAL |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
10000.0 AC ALL LOCATIONS |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
2.750 INCHES NOMINAL |
| AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
1.031 INCHES NOMINAL |
| FEAT |
SPECIAL FEATURES |
MAIN CONTACTS PROTECTED BY ARCING CONTACTS,ARC BARRIERS AND MAGNETIC BLOWOUTS; MAIN CONTACTS SELF-ALIGNING,SELF-CLEANING AND REMOVABLE |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CPRQ |
RESET METHOD |
MANUAL |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
280.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 950.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| ADAT |
BODY WIDTH |
8.000 INCHES MINIMUM AND 8.500 INCHES MAXIMUM |
| SPCL |
SPECIAL TEST FEATURES |
DIELECTRIC STRENGTH MUST PASS EQUIVALENT OF 1960V BETWEEN LIVE PARTS AND GROUND AND BETWEEN POLES FOR 1 SECOND IN BOTH OPEN AND CLOSED POSITIONS; MUST INTERRUPT 350 PERCENT AT 60 HZ OF ITS RATED CURRENT AT 208V FOR 30 OPERATIONS AT 10 SECOND INTERVALS WITHOUT UNDUE BURNING OF CONTACTS |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
14.750 INCHES NOMINAL |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
600.0 AC ALL LOCATIONS |