ABHP |
OVERALL LENGTH |
10.125 INCHES NOMINAL |
ABMK |
OVERALL WIDTH |
5.500 INCHES NOMINAL |
TTQY |
TERMINAL TYPE AND QUANTITY |
6 TAB, SOLDER LUG |
CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
AKPX |
POLE QUANTITY |
3 |
CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE, TWO, AND THREE LINKED |
AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
3 TOGGLE |
CPRZ |
AUXILIARY SWITCH FUNCTION AND QUANTITY |
1 CONTROL |
CPRJ |
TRIP RELEASE METHOD |
THERMAL ALL LOCATIONS |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
208.0 AMPERES AC ALL LOCATIONS |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
130.0 ALL LOCATIONS |
FEAT |
SPECIAL FEATURES |
UNDERV0LTAGE PROTECTION DEVICE WITH 60 INCH LEADS INCLUDED |
ADTV |
CASE MATERIAL |
PLASTIC |
AAQL |
BODY STYLE |
RECTANGULAR DIMENSIONAL ENVELOPE |
CPRQ |
RESET METHOD |
MANUAL |
CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
AEGJ |
SWITCH CONTACT ARRANGEMENT |
SINGLE POLE, SINGLE THROW, NORMALLY OPEN |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
77.0 DEG FAHRENHEIT NOMINAL ALL LOCATIONS |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
9.000 MINIMUM AT 130 PCT ALL LOCATIONS AND 120.000 MAXIMUM AT 130 PCT ALL LOCATIONS AND 60.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 250.000 MAXIMUM AT 150 PCT ALL LOCATIONS |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
CRTK |
SWITCH TERMINAL TYPE |
WIRE LEAD |
ABKW |
OVERALL HEIGHT |
4.812 INCHES NOMINAL |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
600.0 AC ALL LOCATIONS |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
25000.0 AC ALL LOCATIONS |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
GENERAL PURPOSE |