FREQ |
FREQUENCY IN HERTZ |
400.0 ALL LOCATIONS |
CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
2000.0 AC ALL LOCATIONS |
AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
3.359 INCHES NOMINAL |
AKPX |
POLE QUANTITY |
3 |
CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE, TWO, AND THREE LINKED |
CPRP |
ULTIMATE TRIP TIME PER POLE IN SECONDS |
11.000 MINIMUM ALL LOCATIONS AND 70.000 MAXIMUM ALL LOCATIONS |
ADAT |
BODY WIDTH |
3.052 INCHES NOMINAL |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT AND MOISTURE RESISTANT |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
AJEC |
BOSS HEIGHT |
0.156 INCHES NOMINAL |
AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
1.031 INCHES NOMINAL |
ADTV |
CASE MATERIAL |
PLASTIC |
CPRQ |
RESET METHOD |
MANUAL |
AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.750 INCHES NOMINAL |
THSD |
THREAD SERIES DESIGNATOR |
UNC |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
6 THREADED HOLE |
CPRJ |
TRIP RELEASE METHOD |
MAGNETIC-HYDRAULIC ALL LOCATIONS |
AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
3.063 INCHES NOMINAL |
AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
1.031 INCHES NOMINAL |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
4.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 10.700 MAXIMUM AT 200 PCT ALL LOCATIONS AND 0.700 MINIMUM AT 400 PCT ALL LOCATIONS AND 1.100 MAXIMUM AT 400 PCT ALL LOCATIONS |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
ADAQ |
BODY LENGTH |
3.719 INCHES NOMINAL |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
120.0 AC ALL LOCATIONS |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
TTQY |
TERMINAL TYPE AND QUANTITY |
6 THREADED STUD |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
150.0 ALL LOCATIONS |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |
CMLP |
THREAD QUANTITY PER INCH |
32 |
CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
50.0 AMPERES AC ALL LOCATIONS |