CPSF |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS |
+280.0/+460.0 AC ALL LOCATIONS AND +1750.0/+5250.0 AC ALL LOCATIONS |
CPRP |
ULTIMATE TRIP TIME PER POLE IN SECONDS |
56.000 NOMINAL ALL LOCATIONS |
FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
10.562 INCHES NOMINAL |
TTQY |
TERMINAL TYPE AND QUANTITY |
6 BUS BAR |
AKPX |
POLE QUANTITY |
3 |
CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE, TWO, AND THREE LINKED |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
3500.0 AC ALL LOCATIONS |
CPRZ |
AUXILIARY SWITCH FUNCTION AND QUANTITY |
12 ALARM |
CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SHUNT TRIP ALL LOCATIONS |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
600.0 AMPERES AC ALL LOCATIONS |
CSWP |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS |
208.0 AC AND 120.0 DC |
CPRQ |
RESET METHOD |
ELECTRIC |
AEGJ |
SWITCH CONTACT ARRANGEMENT |
SINGLE POLE, DOUBLE THROW |
CQTL |
RESET ACTUATOR VOLTAGE RATING AND TYPE IN VOLTS |
208.0 AC |
CBBL |
FEATURES PROVIDED |
ADJUSTABLE TRIP RELEASE |
AJEC |
BOSS HEIGHT |
0.375 INCHES NOMINAL |
ADAQ |
BODY LENGTH |
17.562 INCHES NOMINAL |
CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRW |
ACTUATOR FUNCTION |
RESET |
ADAU |
BODY HEIGHT |
17.000 INCHES NOMINAL |
CPRJ |
TRIP RELEASE METHOD |
MAGNETIC ALL LOCATIONS |
AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
1.375 INCHES NOMINAL |
ADAT |
BODY WIDTH |
12.750 INCHES NOMINAL |
FEAT |
SPECIAL FEATURES |
LONG DELAY PICKUP,LONG TIME DELAYBAND,INSTANTANEOUS PICKUP SETTINGS ADJUSTABLE. |
CRTK |
SWITCH TERMINAL TYPE |
THREADED STUD |
ABTD |
MOUNTING SLOT WIDTH |
0.187 INCHES NOMINAL |
AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
11.625 INCHES NOMINAL |
ADTV |
CASE MATERIAL |
METAL |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
3.625 INCHES NOMINAL |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE ONE |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 ROTARY |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
150.0 ALL LOCATIONS |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 SLOT AND 4 UNTHREADED HOLE |
CSSX |
SWITCH CURRENT RATING AND TYPE IN AMPS |
12.0 AC AND 9.0 DC |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
1000.000 MAXIMUM AT 100 PCT ALL LOCATIONS AND 56.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 46.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 75.000 MINIMUM AT 100 PCT ALL LOCATIONS AND 34.000 MINIMUM AT 400 PCT ALL LOCATIONS AND 200.000 MAXIMUM AT 150 PCT ALL LOCATIONS AND 90.000 MAXIMUM AT 400 PCT ALL LOCATIONS AND 28.000 MINIMUM AT 500 PCT ALL LOCATIONS AND 150.000 MAXIMUM AT 300 PCT ALL LOCATIONS AND 40.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 65.000 MAXIMUM AT 500 PCT ALL LOCATIONS AND 300.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 10.000 MINIMUM AT 1000 PCT ALL LOCATIONS AND 18.000 MAXIMUM AT 1000 PCT ALL LOCATIONS |
AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.500 INCHES NOMINAL |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
600.0 AC ALL LOCATIONS |