AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
4.349 INCHES MINIMUM AND 4.369 INCHES MAXIMUM |
CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 UNTHREADED HOLE |
AJEC |
BOSS HEIGHT |
0.208 INCHES MINIMUM AND 0.228 INCHES MAXIMUM |
BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE TWO |
AKPX |
POLE QUANTITY |
3 |
AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
25.0 AMPERES DC ALL LOCATIONS |
AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
3.302 INCHES MINIMUM AND 3.322 INCHES MAXIMUM |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
DUSTPROOF AND FUNGUS PROOF |
ADTV |
CASE MATERIAL |
PLASTIC |
AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
4.349 INCHES MINIMUM AND 4.369 INCHES MAXIMUM |
CPRQ |
RESET METHOD |
MANUAL |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
3.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.190 INCHES NOMINAL |
ADAQ |
BODY LENGTH |
5.240 INCHES MINIMUM AND 5.260 INCHES MAXIMUM |
CPRJ |
TRIP RELEASE METHOD |
MAGNETIC-HYDRAULIC ALL LOCATIONS |
AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
0.990 INCHES MINIMUM AND 1.010 INCHES MAXIMUM |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
ADAT |
BODY WIDTH |
2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
APNQ |
ARC QUENCHING METHOD |
MAGNETIC BLOWOUT |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
125.0 DC ALL LOCATIONS |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
TTQY |
TERMINAL TYPE AND QUANTITY |
6 THREADED STUD |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
5000.0 DC ALL LOCATIONS |
AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
0.990 INCHES MINIMUM AND 1.010 INCHES MAXIMUM |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |