AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
0.552 INCHES MINIMUM AND 0.578 INCHES MAXIMUM |
BBRJ |
SPECIAL HANDLING FEATURE |
MAGNETIC |
FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
4.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
2 TOGGLE |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
40.0 AMPERES AC ALL LOCATIONS |
AKPX |
POLE QUANTITY |
2 |
AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
CORROSION RESISTANT |
ZZZK |
SPECIFICATION/STANDARD DATA |
81348-W-C-375/6 GOVERNMENT SPECIFICATION |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
10000.0 AC ALL LOCATIONS |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
AJEC |
BOSS HEIGHT |
0.188 INCHES NOMINAL |
ADAT |
BODY WIDTH |
1.464 INCHES MINIMUM AND 1.496 INCHES MAXIMUM |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
240.0 AC ALL LOCATIONS |
ADTV |
CASE MATERIAL |
PLASTIC |
CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRQ |
RESET METHOD |
MANUAL |
ADAQ |
BODY LENGTH |
2.987 INCHES MINIMUM AND 3.013 INCHES MAXIMUM |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
135.0 ALL LOCATIONS |
CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
ADAU |
BODY HEIGHT |
2.312 INCHES NOMINAL |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
2 TERMINAL |
TEST |
TEST DATA DOCUMENT |
81348-W-C-375 SPECIFICATION |
CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE AND TWO LINKED |
TTQY |
TERMINAL TYPE AND QUANTITY |
4 CLIP |