CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
15.0 AMPERES AC ALL LOCATIONS |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
2 TOGGLE |
AKPX |
POLE QUANTITY |
2 |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
1500.0 AC ALL LOCATIONS |
TTQY |
TERMINAL TYPE AND QUANTITY |
4 THREADED STUD |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT AND MOISTURE RESISTANT |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
ADAT |
BODY WIDTH |
2.031 INCHES NOMINAL |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
AJEC |
BOSS HEIGHT |
0.156 INCHES NOMINAL |
AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
1.031 INCHES NOMINAL |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 THREADED HOLE |
ADTV |
CASE MATERIAL |
PLASTIC |
CPRQ |
RESET METHOD |
MANUAL |
AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.750 INCHES NOMINAL |
THSD |
THREAD SERIES DESIGNATOR |
UNC |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
13.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 40.000 MAXIMUM AT 150 PCT ALL LOCATIONS AND 1.000 MINIMUM AT 400 PCT ALL LOCATIONS AND 3.000 MAXIMUM AT 400 PCT ALL LOCATIONS |
CPRJ |
TRIP RELEASE METHOD |
MAGNETIC-HYDRAULIC ALL LOCATIONS |
AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
3.063 INCHES NOMINAL |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
1.031 INCHES NOMINAL |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
CPRP |
ULTIMATE TRIP TIME PER POLE IN SECONDS |
10.000 MINIMUM ALL LOCATIONS AND 80.000 MAXIMUM ALL LOCATIONS |
AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
3.427 INCHES NOMINAL |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ |
BODY LENGTH |
3.719 INCHES NOMINAL |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
250.0 AC ALL LOCATIONS |
CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE AND TWO LINKED |
CMLP |
THREAD QUANTITY PER INCH |
32 |
FREQ |
FREQUENCY IN HERTZ |
50.0 ALL LOCATIONS |
CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |