CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
42.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 180.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ABHP |
OVERALL LENGTH |
4.375 INCHES NOMINAL |
FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
ABMK |
OVERALL WIDTH |
3.000 INCHES NOMINAL |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE TWO |
AKPX |
POLE QUANTITY |
3 |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
6 TERMINAL |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
5000.0 AC ALL LOCATIONS |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
240.0 AC ALL LOCATIONS |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
100.0 AMPERES AC ALL LOCATIONS |
ADTV |
CASE MATERIAL |
PLASTIC |
CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
AAQL |
BODY STYLE |
RECTANGULAR DIMENSIONAL ENVELOPE |
ABKW |
OVERALL HEIGHT |
2.812 INCHES NOMINAL |
CPRQ |
RESET METHOD |
MANUAL |
TTQY |
TERMINAL TYPE AND QUANTITY |
3 COMPRESSION AND 3 CLIP |
CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
DUSTPROOF |