CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
1000.0 AC ALL LOCATIONS |
FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
1.180 INCHES MINIMUM AND 1.200 INCHES MAXIMUM |
AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
2 TOGGLE |
AKPX |
POLE QUANTITY |
2 |
CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
2.800 MINIMUM AT 200 PCT ALL LOCATIONS AND 8.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
30.0 AMPERES AC ALL LOCATIONS |
CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 THREADED HOLE |
CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
DUSTPROOF AND FUNGUS PROOF |
AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
1.990 INCHES MINIMUM AND 2.010 INCHES MAXIMUM |
ADTV |
CASE MATERIAL |
PLASTIC |
TTQY |
TERMINAL TYPE AND QUANTITY |
4 TAB W/SCREW |
CPRQ |
RESET METHOD |
MANUAL |
ABXD |
BUSHING LENGTH |
0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM |
THSD |
THREAD SERIES DESIGNATOR |
UNC |
CPRJ |
TRIP RELEASE METHOD |
MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
ADAQ |
BODY LENGTH |
2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
ADAT |
BODY WIDTH |
1.510 INCHES MINIMUM AND 1.530 INCHES MAXIMUM |
APNQ |
ARC QUENCHING METHOD |
MAGNETIC BLOWOUT |
CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
250.0 AC ALL LOCATIONS |
AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE AND TWO LINKED |
CMLP |
THREAD QUANTITY PER INCH |
32 |
CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |
AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
1.802 INCHES MINIMUM AND 1.822 INCHES MAXIMUM |