| FREQ |
FREQUENCY IN HERTZ |
400.0 ALL LOCATIONS |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
40.0 AMPERES AC ALL LOCATIONS |
| AKPX |
POLE QUANTITY |
3 |
| CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE, TWO, AND THREE LINKED |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
3 TOGGLE |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
1500.0 AC ALL LOCATIONS |
| CPRP |
ULTIMATE TRIP TIME PER POLE IN SECONDS |
70.000 NOMINAL ALL LOCATIONS |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM |
| AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
3.310 INCHES MAXIMUM |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
3.050 INCHES MINIMUM AND 3.070 INCHES MAXIMUM |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CPRQ |
RESET METHOD |
MANUAL |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
| ADAT |
BODY WIDTH |
3.060 INCHES MAXIMUM |
| THSD |
THREAD SERIES DESIGNATOR |
UNC |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
6 THREADED HOLE |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| AJEC |
BOSS HEIGHT |
0.145 INCHES MINIMUM AND 0.175 INCHES MAXIMUM |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
| AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
2.040 INCHES MINIMUM AND 2.080 INCHES MAXIMUM |
| TTQY |
TERMINAL TYPE AND QUANTITY |
6 THREADED STUD |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
150.0 ALL LOCATIONS |
| ADAQ |
BODY LENGTH |
3.790 INCHES MAXIMUM |
| CMLP |
THREAD QUANTITY PER INCH |
32 |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
DUSTPROOF |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
2.060 INCHES NOMINAL |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
416.0 AC ALL LOCATIONS |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
8.000 NOMINAL AT 400 PCT ALL LOCATIONS |
| CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |