| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
10.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 60.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
138.0 ALL LOCATIONS |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
EXPLOSION PROOF |
| AKPX |
POLE QUANTITY |
3 |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
7.5 AMPERES AC ALL LOCATIONS |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
1500.0 AC ALL LOCATIONS |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 THREADED HOLE |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
1.813 INCHES NOMINAL |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CPRQ |
RESET METHOD |
MANUAL |
| APNQ |
ARC QUENCHING METHOD |
AIR |
| CPRW |
ACTUATOR FUNCTION |
RESET |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
1.500 INCHES NOMINAL |
| THSD |
THREAD SERIES DESIGNATOR |
UNC |
| ABKW |
OVERALL HEIGHT |
3.000 INCHES NOMINAL |
| CPRJ |
TRIP RELEASE METHOD |
MAGNETIC ALL LOCATIONS |
| ABMK |
OVERALL WIDTH |
2.203 INCHES NOMINAL |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 PUSH-PULL |
| TTQY |
TERMINAL TYPE AND QUANTITY |
6 SCREW |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
120.0 AC ALL LOCATIONS |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| ABHP |
OVERALL LENGTH |
2.250 INCHES NOMINAL |
| CMLP |
THREAD QUANTITY PER INCH |
32 |
| CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |