| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 UNTHREADED HOLE |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| AKPX |
POLE QUANTITY |
3 |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
14.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 110.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 47.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 29.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
10000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CPRQ |
RESET METHOD |
MANUAL |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| TTQY |
TERMINAL TYPE AND QUANTITY |
6 SCREW |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
90.0 AMPERES AC ALL LOCATIONS AND 90.0 AMPERES DC ALL LOCATIONS |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |