| ABKW |
OVERALL HEIGHT |
3.500 INCHES NOMINAL |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
225.0 AMPERES AC ALL LOCATIONS AND 225.0 AMPERES DC ALL LOCATIONS |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
500.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
| TTQY |
TERMINAL TYPE AND QUANTITY |
6 BUS BAR |
| AKPX |
POLE QUANTITY |
3 |
| AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.438 INCHES NOMINAL |
| ABHP |
OVERALL LENGTH |
7.531 INCHES NOMINAL |
| ABMK |
OVERALL WIDTH |
3.688 INCHES NOMINAL |
| CBBL |
FEATURES PROVIDED |
ADJUSTABLE TRIP RELEASE |
| AAQL |
BODY STYLE |
RECTANGULAR DIMENSIONAL ENVELOPE |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
3 UNTHREADED HOLE |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
60.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 120.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
| CPSF |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS |
+1500.0/+3000.0 AC ALL LOCATIONS AND +1770.0/+3550.0 DC ALL LOCATIONS |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
150.0 ALL LOCATIONS |