| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
100.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 190.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| ABMK |
OVERALL WIDTH |
2.750 INCHES NOMINAL |
| AKPX |
POLE QUANTITY |
2 |
| CPRX |
ACTUATOR POSITION DESIGNATION |
BETWEEN POLE ONE AND TWO |
| ABHP |
OVERALL LENGTH |
6.312 INCHES NOMINAL |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
| TTQY |
TERMINAL TYPE AND QUANTITY |
4 COMPRESSION |
| ZZZK |
SPECIFICATION/STANDARD DATA |
81348-W-C-375/11 GOVERNMENT SPECIFICATION |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT |
| ADTV |
CASE MATERIAL |
PLASTIC |
| AAQL |
BODY STYLE |
RECTANGULAR DIMENSIONAL ENVELOPE |
| CPRQ |
RESET METHOD |
MANUAL |
| ABKW |
OVERALL HEIGHT |
4.156 INCHES NOMINAL |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
90.0 AMPERES AC ALL LOCATIONS AND 90.0 AMPERES DC ALL LOCATIONS |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
240.0 AC ALL LOCATIONS AND 125.0 DC ALL LOCATIONS |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| TEST |
TEST DATA DOCUMENT |
81348-W-C-375 SPECIFICATION |
| AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.187 INCHES NOMINAL |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
2 UNTHREADED HOLE |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
7500.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS |