| CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
2000.0 AC ALL LOCATIONS |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
11.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 1.500 MINIMUM AT 300 PCT ALL LOCATIONS AND 10.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 4.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 30.000 MAXIMUM AT 150 PCT ALL LOCATIONS AND 4.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
| AKPX |
POLE QUANTITY |
3 |
| CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE, TWO, AND THREE LINKED |
| AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
2.471 INCHES NOMINAL |
| AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
3 TOGGLE |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT AND MOISTURE RESISTANT |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.062 INCHES NOMINAL |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
5.0 AMPERES AC ALL LOCATIONS |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
0.750 INCHES NOMINAL |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
| ADAT |
BODY WIDTH |
2.250 INCHES NOMINAL |
| ADAQ |
BODY LENGTH |
2.500 INCHES NOMINAL |
| ADTV |
CASE MATERIAL |
PLASTIC |
| AJEC |
BOSS HEIGHT |
0.140 INCHES NOMINAL |
| CPRQ |
RESET METHOD |
MANUAL |
| THSD |
THREAD SERIES DESIGNATOR |
UNC |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
1.938 INCHES NOMINAL |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
6 THREADED HOLE |
| CPRJ |
TRIP RELEASE METHOD |
MAGNETIC-HYDRAULIC ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| APNQ |
ARC QUENCHING METHOD |
MAGNETIC BLOWOUT |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
| AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
120.0 AC ALL LOCATIONS |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| TTQY |
TERMINAL TYPE AND QUANTITY |
6 THREADED STUD |
| PKWT |
UNPACKAGED UNIT WEIGHT |
14.000 OUNCES |
| CMLP |
THREAD QUANTITY PER INCH |
32 |
| CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
0.750 INCHES NOMINAL |