| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 UNTHREADED HOLE |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| ADAQ |
BODY LENGTH |
6.312 INCHES NOMINAL |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE TWO |
| ADAU |
BODY HEIGHT |
3.140 INCHES NOMINAL |
| AKPX |
POLE QUANTITY |
2 |
| AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
40.0 AMPERES AC ALL LOCATIONS AND 40.0 AMPERES DC ALL LOCATIONS |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
4.620 INCHES NOMINAL |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
4.620 INCHES NOMINAL |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| ADAT |
BODY WIDTH |
2.750 INCHES NOMINAL |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
1.375 INCHES NOMINAL |
| TTQY |
TERMINAL TYPE AND QUANTITY |
4 SCREW |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CPRQ |
RESET METHOD |
MANUAL |
| APNQ |
ARC QUENCHING METHOD |
AIR |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
1.380 INCHES NOMINAL |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
18000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
| AJEC |
BOSS HEIGHT |
0.710 INCHES NOMINAL |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
10.0 DEG CELSIUS MINIMUM ALL LOCATIONS AND 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
725.000 MINIMUM AT 100 PCT ALL LOCATIONS AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 9.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 18.000 MAXIMUM AT 400 PCT ALL LOCATIONS AND 12.000 MAXIMUM AT 500 PCT ALL LOCATIONS AND 0.440 MINIMUM AT 1000 PCT ALL LOCATIONS AND 2.400 MAXIMUM AT 1000 PCT ALL LOCATIONS AND 15.000 MINIMUM AT 250 PCT ALL LOCATIONS AND 30.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 37.500 MAXIMUM AT 300 PCT ALL LOCATIONS AND 4.250 MINIMUM AT 400 PCT ALL LOCATIONS AND 60.000 MAXIMUM AT 250 PCT ALL LOCATIONS AND 1000.000 MAXIMUM AT 100 PCT ALL LOCATIONS AND 2.400 MINIMUM AT 500 PCT ALL LOCATIONS AND 0.590 NOMINAL AT 2000 PCT ALL LOCATIONS |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| CBME |
CUBIC MEASURE |
55.314 CUBIC INCHES |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
480.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |