| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 UNTHREADED HOLE |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| TTQY |
TERMINAL TYPE AND QUANTITY |
4 SCREW BASE |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
25000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
150.0 AMPERES AC ALL LOCATIONS |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CPRQ |
RESET METHOD |
MANUAL |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
| AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.190 INCHES NOMINAL |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
140.000 MAXIMUM AT 250 PCT ALL LOCATIONS AND 30.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 300.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 100.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 50.000 MINIMUM AT 250 PCT ALL LOCATIONS AND 80.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
| CPRW |
ACTUATOR FUNCTION |
TRIP W/SEPARATE RESET |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |