| CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| AKPX |
POLE QUANTITY |
4 |
| ADAQ |
BODY LENGTH |
2.475 INCHES MINIMUM AND 2.505 INCHES MAXIMUM |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
1000.0 AC ALL LOCATIONS AND 1000.0 DC ALL LOCATIONS |
| ADAT |
BODY WIDTH |
3.000 INCHES MINIMUM AND 3.015 INCHES MAXIMUM |
| TTQY |
TERMINAL TYPE AND QUANTITY |
8 THREADED STUD |
| AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
| AJEC |
BOSS HEIGHT |
0.135 INCHES MINIMUM AND 0.165 INCHES MAXIMUM |
| AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
2.445 INCHES MINIMUM AND 2.475 INCHES MAXIMUM |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.045 INCHES MINIMUM AND 2.065 INCHES MAXIMUM |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
4 TOGGLE |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
30.0 AMPERES AC ALL LOCATIONS AND 30.0 AMPERES DC ALL LOCATIONS |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPRY |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT |
ONE, TWO, THREE, AND FOUR LINKED |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
0.735 INCHES MINIMUM AND 0.765 INCHES MAXIMUM |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
2.200 MINIMUM AT 200 PCT ALL LOCATIONS AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT |
| ADTV |
CASE MATERIAL |
PLASTIC |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
8 THREADED HOLE |
| CPRQ |
RESET METHOD |
MANUAL |
| THSD |
THREAD SERIES DESIGNATOR |
UNC |
| CPRJ |
TRIP RELEASE METHOD |
MAGNETIC ALL LOCATIONS |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
1.925 INCHES MINIMUM AND 1.955 INCHES MAXIMUM |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| PKWT |
UNPACKAGED UNIT WEIGHT |
12.500 OUNCES |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| APNQ |
ARC QUENCHING METHOD |
MAGNETIC BLOWOUT |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
| AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| CBBL |
FEATURES PROVIDED |
HIGH INRUSH PROTECTION |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
0.735 INCHES MINIMUM AND 0.755 INCHES MAXIMUM |
| CMLP |
THREAD QUANTITY PER INCH |
32 |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
250.0 AC ALL LOCATIONS AND 65.0 DC ALL LOCATIONS |
| CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |