| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
| FREQ |
FREQUENCY IN HERTZ |
60.0 SINGLE LOCATION |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| CPRJ |
TRIP RELEASE METHOD |
MAGNETIC-HYDRAULIC SINGLE LOCATION |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT SINGLE LOCATION |
| AAQL |
BODY STYLE |
SINGLE POLE TYPE |
| AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
| TTQY |
TERMINAL TYPE AND QUANTITY |
2 THREADED STUD |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
240.0 AC SINGLE LOCATION |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
12.0 AMPERES AC SINGLE LOCATION |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
5000.0 AC SINGLE LOCATION |
| CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP SINGLE LOCATION |
| ADAT |
BODY WIDTH |
0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
0.300 MINIMUM AT 400 PCT SINGLE LOCATION AND 2.000 MAXIMUM AT 400 PCT SINGLE LOCATION AND 20.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 2.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 0.003 MINIMUM AT 1000 PCT SINGLE LOCATION AND 0.040 MAXIMUM AT 1000 PCT SINGLE LOCATION |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPRP |
ULTIMATE TRIP TIME PER POLE IN SECONDS |
1.000 MINIMUM SINGLE LOCATION AND 6.000 MAXIMUM SINGLE LOCATION |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
DUSTPROOF AND FUNGUS PROOF |
| ADTV |
CASE MATERIAL |
PLASTIC |
| AKPX |
POLE QUANTITY |
1 |
| CPRQ |
RESET METHOD |
MANUAL |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
2 THREADED HOLE |
| THSD |
THREAD SERIES DESIGNATOR |
UNC |
| CPRW |
ACTUATOR FUNCTION |
TRIP W/SEPARATE RESET |
| ADAQ |
BODY LENGTH |
2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
| APNQ |
ARC QUENCHING METHOD |
MAGNETIC BLOWOUT |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE ONE |
| AJEC |
BOSS HEIGHT |
0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| CMLP |
THREAD QUANTITY PER INCH |
32 |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY SINGLE LOCATION |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 SINGLE LOCATION |
| CQJX |
NOMINAL THREAD SIZE |
0.138 INCHES |
| AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
2.611 INCHES NOMINAL |