| CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP ALL LOCATIONS |
| BBRJ |
SPECIAL HANDLING FEATURE |
MAGNETIC |
| ADAQ |
BODY LENGTH |
6.500 INCHES NOMINAL |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| CSSX |
SWITCH CURRENT RATING AND TYPE IN AMPS |
15.0 AC |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE TWO |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
500.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
| AKPX |
POLE QUANTITY |
3 |
| CPRZ |
AUXILIARY SWITCH FUNCTION AND QUANTITY |
1 ALARM |
| CQJX |
NOMINAL THREAD SIZE |
0.190 INCHES |
| AJEC |
BOSS HEIGHT |
0.187 INCHES NOMINAL |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 THREADED STUD |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPSF |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS |
+500.0/+700.0 AC ALL LOCATIONS AND +1200.0/+1400.0 DC ALL LOCATIONS |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY ALL LOCATIONS |
| AGAV |
END ITEM IDENTIFICATION |
T-1434/WQC |
| AEGJ |
SWITCH CONTACT ARRANGEMENT |
SINGLE POLE, DOUBLE THROW |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
15000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
| CQSM |
SWITCH LOCATION AND POSITION DESIGNATION |
INTERNAL AT POLE ONE |
| CBBL |
FEATURES PROVIDED |
ADJUSTABLE TRIP RELEASE |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
1.375 INCHES NOMINAL |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
3600.000 NOMINAL AT 150 PCT ALL LOCATIONS |
| CPRQ |
RESET METHOD |
MANUAL |
| THSD |
THREAD SERIES DESIGNATOR |
UNF |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
3.937 INCHES NOMINAL |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
100.0 AMPERES AC ALL LOCATIONS AND 100.0 AMPERES DC ALL LOCATIONS |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
3.312 INCHES NOMINAL |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
135.0 ALL LOCATIONS |
| CPRJ |
TRIP RELEASE METHOD |
MAGNETIC ALL LOCATIONS |
| CRTK |
SWITCH TERMINAL TYPE |
TAB, SOLDER LUG |
| ADAU |
BODY HEIGHT |
3.875 INCHES NOMINAL |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CSWP |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS |
250.0 AC |
| TTQY |
TERMINAL TYPE AND QUANTITY |
6 THREADED STUD |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
3.687 INCHES NOMINAL |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |
| CMLP |
THREAD QUANTITY PER INCH |
32 |
| ADAT |
BODY WIDTH |
4.125 INCHES NOMINAL |