| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
225.0 AMPERES AC ALL LOCATIONS AND 225.0 AMPERES DC ALL LOCATIONS |
| CPSF |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS |
+1000.0/+2250.0 AC ALL LOCATIONS AND +1000.0/+2250.0 DC ALL LOCATIONS |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 UNTHREADED HOLE |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT SECOND LOCATION |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
1.380 INCHES NOMINAL |
| ADAT |
BODY WIDTH |
4.130 INCHES NOMINAL |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE TWO |
| AKPX |
POLE QUANTITY |
3 |
| CPRZ |
AUXILIARY SWITCH FUNCTION AND QUANTITY |
1 ALARM |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
7.750 INCHES NOMINAL |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
8.380 INCHES NOMINAL |
| CPRH |
CIRCUIT PROTECTION TYPE |
UNDERVOLTAGE THIRD LOCATION |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| AJEC |
BOSS HEIGHT |
0.250 INCHES NOMINAL |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS |
| ADAQ |
BODY LENGTH |
10.125 INCHES NOMINAL |
| AEGJ |
SWITCH CONTACT ARRANGEMENT |
SINGLE POLE, DOUBLE THROW |
| CQSM |
SWITCH LOCATION AND POSITION DESIGNATION |
INTERNAL AT POLE ONE |
| CBBL |
FEATURES PROVIDED |
ADJUSTABLE TRIP RELEASE |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
FUNGUS RESISTANT |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CPRQ |
RESET METHOD |
MANUAL |
| ADAU |
BODY HEIGHT |
3.810 INCHES NOMINAL |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
1.380 INCHES NOMINAL |
| AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.250 INCHES NOMINAL |
| TTQY |
TERMINAL TYPE AND QUANTITY |
6 COMPRESSION |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
22000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT FIRST LOCATION |