| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 UNTHREADED HOLE |
| CQSM |
SWITCH LOCATION AND POSITION DESIGNATION |
EXTERNAL AT POLE THREE |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS |
| BBRG |
STORAGE TYPE |
GENERAL PURPOSE WAREHOUSE |
| AKPX |
POLE QUANTITY |
3 |
| ABHP |
OVERALL LENGTH |
9.120 INCHES NOMINAL |
| ABMK |
OVERALL WIDTH |
8.240 INCHES MINIMUM AND 8.250 INCHES MAXIMUM |
| AFJN |
FRAGILITY FACTOR |
MODERATELY RUGGED |
| ABKW |
OVERALL HEIGHT |
5.380 INCHES MAXIMUM |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
400.0 AMPERES AC ALL LOCATIONS AND 400.0 AMPERES DC ALL LOCATIONS |
| AEGJ |
SWITCH CONTACT ARRANGEMENT |
SINGLE POLE, DOUBLE THROW |
| CBBL |
FEATURES PROVIDED |
ADJUSTABLE TRIP RELEASE |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CSSX |
SWITCH CURRENT RATING AND TYPE IN AMPS |
6.0 AC AND 0.250 DC |
| AAQL |
BODY STYLE |
RECTANGULAR DIMENSIONAL ENVELOPE |
| CPRQ |
RESET METHOD |
MANUAL |
| CPRZ |
AUXILIARY SWITCH FUNCTION AND QUANTITY |
4 ALARM |
| FEAT |
SPECIAL FEATURES |
48 VDC SHUNT TRIP WITH WIRE LEADS INSTALLED ON RIGHT SIDE OF CIRCUIT BREAKER; 120 VAC MOTOR OPERATOR MOUNTED ON FRONT OF CIRCUIT BREAKER,5.750 INCH LG,3.230 INCH W,10.120 INCH H |
| CSWP |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS |
240.0 AC AND 250.0 DC |
| TTQY |
TERMINAL TYPE AND QUANTITY |
6 COMPRESSION |
| CPSF |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS |
+1200.0/+4000.0 AC ALL LOCATIONS AND +1200.0/+4000.0 DC ALL LOCATIONS |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
125.0 ALL LOCATIONS |
| AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.310 INCHES NOMINAL |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
22000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE ONE |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| CRTK |
SWITCH TERMINAL TYPE |
WIRE LEAD |
| CQXF |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED |
GENERAL PURPOSE |