| FREQ |
FREQUENCY IN HERTZ |
50.0 FIRST LOCATION OR 60.0 FIRST LOCATION OR 400.0 FIRST LOCATION |
| ADAT |
BODY WIDTH |
1.500 INCHES NOMINAL |
| TTQY |
TERMINAL TYPE AND QUANTITY |
5 KNIFE BLADE |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT SECOND LOCATION |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
150.0 SECOND LOCATION |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
2 TOGGLE |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
1.560 INCHES NOMINAL |
| AKPX |
POLE QUANTITY |
2 |
| CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP FIRST LOCATION |
| ADAQ |
BODY LENGTH |
2.000 INCHES NOMINAL |
| CPRJ |
TRIP RELEASE METHOD |
MAGNETIC FIRST LOCATION |
| CQQC |
TRIP RELEASE DUTY CYCLE |
CONTINUOUS SECOND LOCATION |
| CPRJ |
TRIP RELEASE METHOD |
MAGNETIC SECOND LOCATION |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
115.0 AC SECOND LOCATION |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
0.750 INCHES NOMINAL |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
6.000 MINIMUM AT 150 PCT FIRST LOCATION AND 70.000 MAXIMUM AT 150 PCT FIRST LOCATION |
| CQWN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT |
0.400 MINIMUM AT 150 PCT SECOND LOCATION AND 6.000 MAXIMUM AT 150 PCT SECOND LOCATION |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CPRQ |
RESET METHOD |
MANUAL |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
2000.0 AC FIRST LOCATION AND 1000.0 DC FIRST LOCATION |
| FREQ |
FREQUENCY IN HERTZ |
50.0 SECOND LOCATION OR 60.0 SECOND LOCATION OR 400.0 SECOND LOCATION |
| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 CLIP |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
10.0 AMPERES AC FIRST LOCATION AND 10.0 AMPERES DC FIRST LOCATION |
| CPRK |
AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS |
115.0 AC NOMINAL SECOND LOCATION |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
240.0 AC FIRST LOCATION |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY FIRST LOCATION |
| CPRW |
ACTUATOR FUNCTION |
TRIP-RESET |
| AJWX |
MOUNTING SURFACE TO TERMINAL END DISTANCE |
1.950 INCHES MAXIMUM |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT EACH POLE |
| AAQL |
BODY STYLE |
MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
2000.0 AC SECOND LOCATION AND 1000.0 DC SECOND LOCATION |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
1.660 INCHES NOMINAL |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
TIME DELAY SECOND LOCATION |
| CPSM |
INTERNAL TRIP RELEASE CONFIGURATION |
SERIES TRIP W/REMOTE TRIP FEATURE SECOND LOCATION |
| AJEC |
BOSS HEIGHT |
0.130 INCHES NOMINAL |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
10.0 AMPERES AC SECOND LOCATION AND 10.0 AMPERES DC SECOND LOCATION |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT FIRST LOCATION |
| CPRN |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT |
150.0 FIRST LOCATION |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
0.750 INCHES NOMINAL |