| AXHR |
MOUNTING FACILITY TYPE AND QUANTITY |
4 UNTHREADED HOLE |
| ADAT |
BODY WIDTH |
4.130 INCHES NOMINAL |
| AEBP |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH |
5.062 INCHES NOMINAL |
| AKPX |
POLE QUANTITY |
3 |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
NONTRIP FREE |
| FREQ |
FREQUENCY IN HERTZ |
60.0 ALL LOCATIONS OR 50.0 ALL LOCATIONS |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
65000.0 AC ALL LOCATIONS |
| ADAQ |
BODY LENGTH |
6.000 INCHES NOMINAL |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
300.0 AMPERES AC ALL LOCATIONS |
| AGAV |
END ITEM IDENTIFICATION |
HEMP ENDURABLE POWER SYSTEM |
| AEHA |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH |
1.375 INCHES NOMINAL |
| AEBQ |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH |
1.375 INCHES NOMINAL |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CPRQ |
RESET METHOD |
MANUAL |
| AJEC |
BOSS HEIGHT |
0.125 INCHES NOMINAL |
| CXCY |
PART NAME ASSIGNED BY CONTROLLING AGENCY |
MOLDED CASE CIRCUIT BREAKER F-FRAME, 10-225 AMP, TYPE ED |
| FEAT |
SPECIAL FEATURES |
SEALED WITH NON-INTERCHANGABLE TRIP UNITS; SUITABLE FOR REVERSE FEED USE; INCLUDES TERMINALS ON LOAD END ONLY |
| AEBY |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH |
4.500 INCHES NOMINAL |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| AEBV |
UNTHREADED MOUNTING HOLE DIAMETER |
0.164 INCHES NOMINAL |
| ADAU |
BODY HEIGHT |
3.380 INCHES NOMINAL |
| TTQY |
TERMINAL TYPE AND QUANTITY |
3 SCREW |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
240.0 AC ALL LOCATIONS AND 125.0 DC ALL LOCATIONS |
| AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |