| FREQ |
FREQUENCY IN HERTZ |
50.0 ALL LOCATIONS OR 60.0 ALL LOCATIONS |
| AKPX |
POLE QUANTITY |
4 |
| CPRX |
ACTUATOR POSITION DESIGNATION |
AT POLE TWO |
| FEAT |
SPECIAL FEATURES |
DC RATINGS ARE OF 2-POLES OF 3-POLE CIRCUIT; TRIP UNIT - THERMAL AND MAGNETIC ARE ADJUSTABLE; RATED ULTIMATE BREAKING CAPACITIES - 65000.0 AMPS AT 220.0 TO 240.0 VOLTS AC; 25000.0 AMPS AT 380.0 TO 415.0 VOLTS AC; 25000.0 AMPS AT 480.0 VOLTS AC; 18000.0 AMPS AT 600.0 VOLTS AC; 12000.0 AMPS AT 690.0 VOLTS AC; 10000.0 AMPS AT 250.0 VOLTS DC; OVERALL HEIGHT 7.000 INCHES NOMINAL; INCLUDES FREEZE TESTED OPTION (F02) USING SPECIAL LUBRICATION, MECHANICAL OPERATION IS VERIFIED TO MINUS 40.0 DEGREES C; ALSO INCLUDES STANDARD SHUNT TRIP OPTION (SNT120CPK) 120.0 VOLTS AC. 50.0 TO 60.0 HERTZ, 110.0 TO 125.0 VOLTS DC. MOUNTED IN RIGHT-HAND CAVITY LEFT POLE POSITION |
| CPRF |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
| CPRG |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS |
65000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
| CPRR |
MAIN CONTACT TRIPPING MECHANISM TYPE |
TRIP FREE |
| CPRL |
TRIP RELEASE CHARACTERISTIC |
INSTANTANEOUS ALL LOCATIONS |
| ADTV |
CASE MATERIAL |
PLASTIC |
| CRCF |
TRIP RELEASE AMBIENT TEMP RATING |
40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CPRQ |
RESET METHOD |
MANUAL |
| CPRW |
ACTUATOR FUNCTION |
TRIP W/SEPARATE RESET |
| CPRJ |
TRIP RELEASE METHOD |
THERMAL-MAGNETIC ALL LOCATIONS |
| CPLM |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE |
200.0 AMPERES AC ALL LOCATIONS AND 200.0 AMPERES DC ALL LOCATIONS |
| CPRH |
CIRCUIT PROTECTION TYPE |
OVERCURRENT ALL LOCATIONS |
| CPRT |
MANUAL ACTUATOR TYPE AND QUANTITY |
1 TOGGLE |
| AAQL |
BODY STYLE |
MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAT |
BODY WIDTH |
5.340 INCHES NOMINAL |
| ADAU |
BODY HEIGHT |
3.440 INCHES NOMINAL |