| RTSE |
RELATIONSHIP TO SIMILAR EQUIPMENT |
REPLACEMENT/UPGRADE TO 6110-01-227-6851 |
| APHP |
MANUAL OPERATION FACILITY |
PROVIDED |
| AGAV |
END ITEM IDENTIFICATION |
AUTO BUS TRANSFER SWIT ABT-1A2-100 |
| ELEC |
VOLTAGE IN VOLTS |
120.0 |
| FAAZ |
PHASE |
THREE |
| AFTM |
SWITCH POSITION QUANTITY |
2 |
| ANPZ |
INCLOSURE FEATURE |
DRIPPROOF |
| ACZB |
FREQUENCY RATING |
60.0 HERTZ NOMINAL |
| APHJ |
SWITCH ACTION TYPE |
ROTARY |
| FEAT |
SPECIAL FEATURES |
SOLENOID LOCK REPLACED BY WARNING LITE. 2 FUSES WITH BLOWN INDICATORS PROTECT L4 COIL, CTRL PANEL & WIRING IF PREVENTED FROM COMPLETING OPERATION DUE TO BLOCKAGE/OUTSIDE FORCES;2 POSITION CNTRL DISCONNECT SWITCH REPLACES THE 3 POSITION SWITCH. INSURES PROPER SEQUENCING OOF ABT WHEN RESTORED FROM MANUAL TO AUTO OP;CONTROL CONTACT ASSY IS INCORPORATING NON-ADJUSTABLE CAMS,DRIVE LINK BUSHINGS PREVENT OVERTIGHT OF LOCK NUTS, & STRONGER DRIVES LINKAGES REPLACE THE PREVIOUS ASSY. |
| APHH |
SWITCH OPERATION METHOD |
MANUAL |
| AMPS |
CURRENT RATING IN AMPS |
100.0 |
| SUPP |
SUPPLEMENTARY FEATURES |
CHGS MADE TO PREVENT NUISANCE TRANSFERS WHEN BOTH SOURCES ARE ENERGIZED SIMULTANEOUSLY, ALSO WHEN A SHORT OUTAGE OF BOTH SOURCES, WHEN BOTH SOURCES ARE INPHASE. NEW INSTRUCTION PLATE PROVIDES OPERATIONAL INFO WITH NEW REVISIONS AND NEW LAMINATED WIRING CARD ARE PROVIDED. |