| APNX |
INPUT VOLTAGE RATING |
120.0 AC POUNDS PER HOUR WET SINGLE OPERATING POWER RQMT |
| CWGH |
OUTPUT CURRENT RATING |
650.0 AC VOLT-AMPERE MAXIMUM SINGLE POWER OUTPUT |
| CWGW |
POWER SUPPLY OUTPUT CURRENT/VOLTAGE CHARACTERISTICS |
LIMITING VOLTAGE SINGLE POWER OUTPUT |
| CBBL |
FEATURES PROVIDED |
EMI FILTER AND OVER VOLTAGE PROTECTOR AND CURRENT REGULATOR CIRCUIT AND INDICATOR LIGHT AND BATTERY CHARGER AND CIRCUIT BREAKER AND PROGRAMMABLE |
| CWHY |
BATTERY FEATURE AND TYPE |
RECHARGEABLE LEAD ACID CELL |
| ABMK |
OVERALL WIDTH |
4.700 INCHES NOMINAL |
| CWHT |
INPUT CONNECTION QUANTITY |
2 SINGLE OPERATING POWER RQMT |
| CXMX |
BATTERY POWER SUPPLY EMERGENCY OPERATING TIME |
6.0 |
| AKWC |
ELECTRICAL POWER SOURCE RELATIONSHIP |
OPERATING |
| CWHF |
OUTPUT CONNECTION QUANTITY |
6 SINGLE POWER OUTPUT |
| CXMN |
BATTERY SWITCHING TIME |
TWO MILLISECONDS |
| BGHX |
OUTPUT CONTROL QUANTITY |
2 SINGLE POWER OUTPUT |
| APTS |
OUTPUT FREQUENCY RATING |
49.9 HERTZ MINIMUM SINGLE POWER OUTPUT AND 60.1 HERTZ MAXIMUM SINGLE POWER OUTPUT |
| CWWB |
BATTERY RECOVERY TIME |
180.0 |
| APTQ |
INPUT FREQUENCY RATING |
47.5 HERTZ MINIMUM SINGLE OPERATING POWER RQMT AND 63.0 HERTZ MAXIMUM SINGLE OPERATING POWER RQMT |
| ABHP |
OVERALL LENGTH |
14.500 INCHES NOMINAL |
| AMQY |
INSTALLATION DESIGN |
CABINET WITH COMPLETE HARDWARE |
| AYNH |
OPERATING AMBIENT TEMP RANGE |
+32.0/+104.0 DEG FAHRENHEIT |
| BGQR |
OUTPUT WATTAGE RATING |
410.0 WATTS MAXIMUM SINGLE POWER OUTPUT |
| FEAT |
SPECIAL FEATURES |
PROGRAMMING TO AUTOMATICALLY INCREASE OUTPUT UP TO 30 PERCENT WHEN INPUT FALLS BETWEEN 81 VAC TO 106 VAC; AUTOMATICALLY DECREASES OUTPUT UP TO 15 PERCENT WHEN INPUT IS BETWEEN 127 VAC AND 143 VAC; OVERLOAD PROTECTION ON BATTERY-INTERNAL CURRENT LIMITING AND ON LINE CIRCUIT BREAKER; MODEM/10 BASE-T/100 BASE-TX NETWORK CABLE PORT USING SINGLE LINE (2 WIRE, RJ11) OR NETWORK (UTP, RJ45) COMPATIBLE JACKS; BATTERY IS USER REPLACEABLE, HOT SWAPPABLE, SEALED, AND MAINTENANCE FREE; 14 DAY AUTO SELF TEST OF ALL INTERNAL COMPONENTS; LEDS INDICATE WHEN ON LINE, ON BATTERY, UPS OVERLOAD, AND REPLACE BATTERY; ALARMS FOR ON BATTERY, LOW BATTERY, AND UPS OVERLOAD; DATA SAVING UNATTENDED SHUTDOWN, ADVANCED POWER MANAGEMENT AND DIAGNOSTIC SOFTWARE INCLUDED; DB 9 SERIAL INTERFACE PORT; OUTPUT VOLTAGE ON BATTERY IS STEPPED APPROXIMATION TO SINE WAVE OUTPUT AT 115 VAC PLUS OR MINUS 8 PERCENT |
| CWGN |
OUTPUT PHASE |
SINGLE SINGLE POWER OUTPUT |
| CWHJ |
OUTPUT CONNECTION TYPE |
RECEPTACLE, ELECTRICAL SINGLE POWER OUTPUT |
| CWHQ |
INPUT CONNECTION TYPE |
CONNECTOR, PLUG SINGLE OPERATING POWER RQMT |
| ANPM |
INPUT PHASE |
SINGLE SINGLE OPERATING POWER RQMT |
| AKAE |
MAXIMUM OPERATING ALTITUDE RATING |
10000.0 FEET |
| CWWJ |
PROGRAM COMPATIBILITY |
APPLE, IBM COMPATIBLE OR UNIX PERSONAL COMPUTERS |
| BGHY |
OUTPUT CONTROL TYPE |
VOLTAGE RANGE SINGLE POWER OUTPUT |
| APPA |
OUTPUT VOLTAGE RATING |
115.0 AC VOLTS NOMINAL SINGLE POWER OUTPUT |
| CXNJ |
POWER SUPPLIES PROGRAMMED PER SYSTEM |
2 |
| ABKW |
OVERALL HEIGHT |
6.600 INCHES NOMINAL |