| FEAT |
SPECIAL FEATURES |
THIS LOW SULFUR PRODUCT MEETS EPA REQUIREMENTS FOR SULFUR COTENT FOR FUELS USED IN DIESEL POWERED VEHICLES |
| CTDH |
MAXIMUM DISTILLATION LOSS VOLUME PERCENTAGE |
1.5 |
| CSTK |
COPPER CORROSION CLASSIFICATION NUMBER |
1 |
| CSGW |
NATO CODE NUMBER |
F34 |
| CRWW |
MAXIMUM AROMATICS PERCENTAGE BY VOLUME |
25.0 |
| CLFT |
MAXIMUM SULPHUR CONTENT PERCENTAGE BY WEIGHT |
0.05 |
| CSWR |
DENSITY VALUE |
0.775 KILOGRAMS PER LITER MINIMUM AND 0.840 KILOGRAMS PER LITER MAXIMUM |
| CTBQ |
MAXIMUM OLEFINS CONTENT PERCENTAGE BY VOLUME |
5.0 |
| CLFZ |
FREEZING POINT MAXIMUM TEMP |
-47.0 DEG CELSIUS |
| CWAY |
SUPPLY CLASSIFICATION |
BULK |
| CRWZ |
DISTILLATION POINT PERCENTAGE AT MAXIMUM TEMP |
205.0 DEG C AT 10.0 PCT AND 300.0 DEG C AT THE END POINT. |
| CQLQ |
VISCOSITY AT RATED TEMP |
8.00 MAXIMUM -20 DEG CELSIUS |
| ZZZT |
NONDEFINITIVE SPEC/STD DATA |
LS8 CODE |
| CTYG |
DENSITY TEMP |
15.0 DEG CELSIUS |
| CTCF |
MINIMUM HEAT OF COMBUSTION VALUE |
42.8 MEGAJOULES PER KILOGRAM |
| CLWH |
FUEL GRADE CLASSIFICATION |
JP-8 |
| CTJC |
MINIMUM FLASH POINT AND TEST METHOD |
38.0 DEG CELSIUS PENSKY-MARTENS CLOSED CUP |
| CWDB |
MAXIMUM AMOUNT OF EXISTENT GUM |
7.0 |